Out Of Stock
Notify me when its in stock
Main |
|
Trip Unit Technology |
Termal Manyetik Thermal Magnetic |
Device Application |
Motor |
Series |
Tesys |
Product Name |
Tesys Gv2 |
Product Grup |
Gv2Me |
Product Series |
Tesys Gv2 |
Product or Component Type |
Circuit Breaker |
|
|
Environment |
|
|
|
IK Protection Degree |
Ik04 |
IP Protection Degree |
Ip20 'E Conforming to IEC 60529 |
Preventive Maintenance |
Th |
Standarts |
Csa C22.2 No 60947-4-1 |
En/Iec 60947-2 |
|
En/Iec 60947-4-1 |
|
Ul 60947-4-1 |
|
Product Certificates |
Atex |
Bv |
|
Ccc |
|
Csa |
|
Dnv-Gl |
|
Eac |
|
Iecee Cb Scheme |
|
Lros (Lloyds Register Of Shipping) |
|
Rına |
|
Ul |
|
Fire Resistance |
960 °C 'E Conforming to IEC 60695-2-1 |
General Features |
|
[ICS] Rated Services Short Circuit Cut View Capacity |
In 100 % 230/240 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
In 40 % - 400/415 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
In 50 % - 440 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
In 75 % - 500 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
In 75 % - 690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
|
|
[In] Rated Current |
23A |
[Ith] Fresh-Air Thermic Current |
23A 'E Conforming to IEC 60947-4-1 |
[Ue] Rated Nominal Voltage |
690 V Ac 50/60 Hz 'E conforming to IEC 60947-2 |
[Ui] Nominal Insulation Voltage Rated |
690 V Ac 50/60 Hz 'E Conforming To IEC 60947-2 |
[Uimp] Rated İnsulation İmpact Resistance Voltage |
6 Kv 'E Conforming To IEC 60947-2 |
Açma Birimi Derecesi Trip Unit Degree |
17-23A |
Network Frequency |
50/60 Hz 'E Conforming To IEC 60947-4-1 |
|
|
Terminals |
Screw Clamp Terminals 2 Cables 1.5-6 Mm² Elastic Cable Jagless |
Screw Clamp Terminals 2 Cables 1-4 Mm² With Elastic |
|
Screw Clamp Terminals 2 Cables 1-6 Mm² Solid |
|
Working Position |
Any Position |
Depth |
78.5 Mm |
Direct Connector |
Without |
Electrical durability |
100000 for Cycles Ac-3 -De 440 V |
Phase failure sensitivity |
Yes 'E Conforming to IEC 60947-4-1 |
Widht |
45 Mm |
|
|
Cut View Capacity |
In 15 Ka Icu - 400/415 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
In 3 Ka Icu – 690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
In 4 Ka Icu - 500 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
In 50 Ka Icu – 230/240 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
In 6 Ka Icu -De 440 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
Control Type |
Open-Close Button |
Usage Category |
Ac-3 'E Conforming to IEC 60947-4-1 |
Category A 'E Conforming to IEC 60947-2 |
|
|
|
Power Dissipation per Pole |
2.5 W |
Number of Pole |
3P |
Magnetic Openning Current |
327-327 A |
Maximum Operating Rate |
25 Cyc/H |
Mechanical Durability |
100000 Cycles |
Motor Power Kw |
In 11-11 Kw - 690 V Ac 50/60 Hz |
In 18.5-18.5 Kw - 400/415 V Ac 50/60 Hz |
|
In 9-9 Kw - 500 V Ac 50/60 Hz |
|
|
|
Rated Duty |
Continuous Conforming to IEC 60947-4-1 |
Fixing Mode |
35 Mm Symmetrical DIN Rail Clipped Panel Screwed (With Adaptor Plate) |
Tightening torque |
1.7 N.m - on screw clamp terminal |
Network Type |
Ac |
Compatibility Code |
Gv2Me |
Product Weight |
0.26 Kg |
Suitability for isolation |
Yes 'E Conforming to IEC 60947-1 |
Height |
89 Mm |