Basic |
|
Opening Unit Technology |
Thermal Magnetic |
Device Application |
Motor |
Series |
Tesys |
Product Name |
Tesys Gv2 |
Product Group |
Gv2Me |
Product Series |
Tesys Gv2 |
Product or Component Type |
Circuit Breaker |
Characteristic |
|
Ambient Air Condition for Operating |
-20-60 °C |
Operating altitude |
2000 M |
Environmental Characteristic for Storage |
-40-80 °C |
IK Protection Degree |
Ik04 |
IP Protection Degree |
Ip20 'E Conforming to IEC 60529 |
Preventive Maintenance |
Th |
Standards |
Csa C22.2 No 60947-4-1 |
En/Iec 60947-2 |
|
En/Iec 60947-4-1 |
|
Ul 60947-4-1 |
|
Product Certificates |
Atex |
Bv |
|
Ccc |
|
Csa |
|
Dnv-Gl |
|
Eac |
|
Iecee Cb Scheme |
|
Lros (Lloyds Register Of Shipping) |
|
Rına |
|
Ul |
|
Flame Vetarder |
960 °C 'E Conforming to IEC 60695-2-1 |
General Features |
|
[Ics] Rated Service Short-time Breaking Capacity |
100 % -De 230/240 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
40 % -De 400/415 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
50 % -De 440 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
75 % -De 500 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
75 % -De 690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
[In] Rated Current |
25 A |
[Ith] Classic Open-air Thermic Current |
25 A 'E Conforming to IEC 60947-4-1 |
[Ue] Rated Operating Voltage |
690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
[Ui] Rated Insulation Voltage |
690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
[Uimp] Rated Impulse Withstand Voltage |
6 Kv 'E Conforming to IEC 60947-2 |
Opening Unit Degree |
20-25 A |
Network Frequency |
50/60 Hz 'E Conforming to IEC 60947-4-1 |
Connections-Terminals |
Screw Clamp Terminals 2 Cables 1.5-6 Mm² Flexible Cable Jagless |
Screw Clamp Terminals 2 Cables 1-4 Mm² Flexible |
|
Screw Clamp Terminals 2 Cables 1-6 Mm² Solid |
|
Operating Location |
Anywhere |
Depth |
78.5 Mm |
Direct Connector |
None |
Electric Durability |
100000 Cycles For Ac-3 -De 440 V |
Phase Fault Sensibility |
Yes 'E Conforming to IEC 60947-4-1 |
Width |
45 Mm |
Breaker Capacity |
15 Ka Icu -De 400/415 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
3 Ka Icu -De 690 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
4 Ka Icu -De 500 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
50 Ka Icu -De 230/240 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
6 Ka Icu -De 440 V Ac 50/60 Hz 'E Conforming to IEC 60947-2 |
|
Control Type |
Opening-Closing Button |
Usage Category |
Ac-3 'E Conforming to IEC 60947-4-1 |
Category A 'E Conforming to IEC 60947-2 |
|
Power Distribution per Pole |
2.5 W |
Pole Description |
3P |
Magnetic Opening Current |
327-327 A |
Maximum Operating Rate |
25 Cyc/H |
Mechanical Durability |
100000 Cycles |
Motor Power Kw |
11-11 Kw -De 400/415 V Ac 50/60 Hz |
15-15 Kw -De 500 V Ac 50/60 Hz |
|
Rated Task |
Continuously 'E Conforming to IEC 60947-4-1 |
Fixing Mode |
35 Mm Symmetric DIN Rail |
Panel: Screwed (With Adaptor Plate) |
|
Tightening Torque |
1.7 N.M Above Screw Clamp Terminals |
Network Type |
Ac |
Compatibility Code |
Gv2Me |
Product Weight |
0.26 Kg |
Compatibility to Insulation |
Yes 'E Conforming to IEC 60947-1 |
Height |
89 Mm |