Technical Data
Nominal AC Voltage (50/60Hz) (L-n) / (n-PE) Uo / un 240 V
Maximum continuous operating voltage (AC) (L-n) / (n-PE) UC 300 V / 305 V
Nominal Discharge Current (8/20 µs) (L-n) / (n-PE) 25 kA / 100 kA
Maximum Discharge Current: (8/20 µs) (L-n) / (n-PE) Imax 65 kA / 130 kA
Nominal Load Current: IL 125 A
Protect Level: (L-n) / (n-PE) until 1500 V / 1500 V
(N - PE) until < 1.5 kV
Total Discharge Current (10/350 µs) total 100 kA
Specific Energy (L - n) / (n - PE) W/r 156 kJ / Ω / 2.5 MJ / Ω
Scharge: (L-n) / (n-PE) Q 12.5 As / 50 As
Voltage Protection Level: (L - N) / (n - PE) up < 1.5 kV / < 1.5 kV < 1.5 kV / < 1.5 kV
Break Spark Polling: (n-PE) Ifı 100 ARMS
Response Time: in (L - n) / (n - PE) < 100 ns / < 100 ns
Spare Fuse: 315 a gG
Rated Short-Circuit current (AC) ISCCR 50 kA
TOV withstand 120 dak (L-N) UT 442 V
TOV withstand 200 MS (n-PE) ut 1200 V
Number of Ports: 1
Mechanical
Terminal Screw Torc: Mmax 39.9 Ibf * ın [4.5 Nm]
Conductor Cut View: 2 AWG (solid, multiwired) / 4 AWG (elastic)
Montage 35 mm DIN Rail, EN 60715
Protection Class: IP 20
Material of Case: Thermoplastic: Quenching Circuit: UL 94 V-0
Thermal Protect: Yes
Working Status / Fault Indication Green Flag / Not Green Flag
Fault Indicator: (L - n) / (n - PE) Red Flag / No
RC Switching Capacity AC: 250 V / 1A, 125 V / 1 A; DC: 48 V / 0.5 a, 24 V / 0.5 a, 12 V / 0.5 A
RC Conductor Cut View: 16 AWG (solid) / 1.5 mm2 (solid)